Model Guides

BWY2 Oil Temperature Indicator Selection Guide

Select a BWY2 oil temperature indicator by range, contacts, Pt100 output, bulb, M27 × 2 thread, capillary length and remote display options.

BWY2-804 and BWY2-806 variants at a Glance

BWY2 selection starts with the top-oil scale and contact requirement. Confirm the full model, -20-140°C range, two to four contacts, Pt100 or optional transmitter output, Φ14 × 150 mm bulb, M27 × 2 thread, capillary length and mounting drawing.

This model guide focuses on selecting the BWY2 OTI configuration for local and remote oil temperature control. Buyers should use the complete model code because the dial family name does not define the final switch count or remote output.

Specifications to Confirm

Selection pointWhat to check
Complete BWY2 model suffixMatch the purchase specification, existing equipment and current model datasheet.
Top-oil temperature scaleMatch the purchase specification, existing equipment and current model datasheet.
Two to four contact functionsMatch the purchase specification, existing equipment and current model datasheet.
Pt100 or transmitter outputMatch the purchase specification, existing equipment and current model datasheet.
Bulb, thread and pocketMatch the purchase specification, existing equipment and current model datasheet.
Capillary and mounting positionMatch the purchase specification, existing equipment and current model datasheet.

Technical Details That Affect the Model Code

The referenced ambient range extends from -40°C to +80°C.

The referenced measuring scale is -20°C to 140°C.

The bulb is Φ14 × 150 mm with M27 × 2 mounting thread.

Do not assume that two instruments with a similar front dial have the same contacts, signal output or capillary assembly.

Replacement and OEM Selection

The stated switch rating is AC 220 V / 5 A.

Protection is referenced as IP55.

A remote display is an option that must match the field output.

For replacement work, send clear photos of the nameplate, terminals, mounting and sensing assembly. For new transformer production, send the approved temperature-control schedule and drawings.

Define the Temperature Value Before Choosing a Controller

A purchasing specification should state exactly what the instrument displays. An oil temperature indicator measures top oil at the transformer thermometer pocket. A traditional winding temperature indicator starts with top-oil temperature and adds a load-current heating effect to simulate winding temperature. These values support different operating decisions and require different model features.

Use the full term in the equipment list and terminal schedule. Avoid a generic tag such as transformer temperature because it can hide whether the value is measured top oil, simulated winding temperature or a separate direct sensor value. Clear naming also helps operators interpret trends and alarms correctly.

For BWY2 oil temperature indicator, ask the transformer designer for the required scale, normal operating range and cooling or protection set points. The controller supplier can provide product data, but transformer-specific thermal limits come from the transformer design and approved protection philosophy.

Specify Cooling, Alarm and Trip Contacts

Temperature controller contacts are normally assigned to defined functions such as fan start, pump start, high-temperature alarm or a trip relay input. List every required contact separately, including its normal state, setting, connected voltage and downstream load. This is more useful than asking only for a controller with several switches.

Compare the instrument contact rating with the actual control circuit. Motors, contactor coils and other inductive loads may require an interposing relay. The control-panel designer should also account for switching tolerance and differential so cooling stages operate in the intended sequence without rapid cycling.

During commissioning, operate each contact and trace the result to the final fan, pump, annunciator or protection input. Record the set point and terminal numbers. This gives purchasing, assembly and maintenance teams one agreed reference for the delivered BWY2-804 and BWY2-806 variants configuration.

Choose Pt100, 4-20 mA or RS485 Remote Output

Pt100 is a resistance signal for a compatible temperature input or remote indicator. Cable resistance and the selected two-wire, three-wire or four-wire arrangement affect how it is connected. A 4-20 mA output is a scaled current loop and requires a defined temperature range, suitable supply and compatible analog input.

RS485 identifies the physical communication layer, not the complete communication specification. A digital monitoring inquiry should also identify protocol, baud rate, address method, parity and register information. The device and PLC, RTU or SCADA system must use matching settings.

Include the receiving equipment in the inquiry. State whether the signal goes to a panel display, PLC analog card, RTU or substation monitoring platform. Ask for the signal scale and wiring diagram, then test the field value against the remote display at more than one point.

Check the Sensing Bulb, Thread and Capillary

The sensing bulb must match the transformer thermometer pocket in diameter, insertion length and mounting thread. A thread designation alone does not confirm that the bulb reaches the correct position or fits the existing pocket. For a replacement, provide photographs and dimensions of both the installed instrument and transformer connection.

Measure the real capillary route from the sensing pocket to the mounting position. Allow enough length for safe routing and service access, but avoid unnecessary tight coils. The capillary is part of a sealed temperature-sensing assembly. It should be protected from crushing, sharp edges, repeated movement and bends tighter than the approved radius.

Also provide the panel cutout, mounting-hole pattern, viewing direction, cable-entry needs and available service space. These mechanical details often determine whether a proposed replacement can be installed without changing the transformer or control cabinet.

Information Needed for a Replacement Controller

Start with the complete existing model code, including every suffix. Add a clear nameplate photo, front view, rear terminals, scale, contact labels and wiring diagram. Record the capillary length, bulb dimensions, mounting thread, enclosure size and mounting-hole positions.

For a winding temperature indicator, include the current-transformer secondary current and the converter, heater or compound-transmitter information. The thermal simulation must match the transformer design. A replacement that fits mechanically can still indicate the wrong simulated temperature if the current input and heating arrangement are different.

Identify any planned change, such as replacing Pt100 with 4-20 mA, adding a remote display or changing the contact functions. Ask the supplier to mark differences between the existing unit and proposed model so the panel designer can review wiring changes before the equipment reaches site.

Documents to Request from the Manufacturer or Supplier

A useful technical offer includes the complete model code, current datasheet, outline drawing and terminal diagram. The datasheet supports range, accuracy, contact and environmental review. The outline drawing confirms enclosure, mounting, bulb and capillary details. The terminal diagram shows how contacts, supply and remote signals are connected.

For supplier qualification or tenders, list the management-system certificates, conformity documents, inspection records or country-specific documents required by the project. Tie each requested document to the product or order instead of asking for a general certificate package.

The commercial inquiry should include quantity, destination, delivery requirement and any inspection or packing requirement. Keeping the technical and commercial scope in one email reduces repeated clarification and makes quotations easier to compare.

Installation and Commissioning Checks

Before installation, compare the received nameplate and accessories with the approved order documents. Inspect the dial, pointer, enclosure, terminals, capillary, protective hose, sensing bulb and thread. Verify power before connecting a powered controller, and use the approved safety procedure whenever a current-transformer circuit is involved.

After installation, check local temperature indication, every cooling or protection contact and every remote output. Confirm that the remote display uses the correct engineering unit and range. For communications, verify address and register mapping. For an analog loop, check the displayed value against the defined signal scale.

Test the controller under conditions that let the team observe the complete signal path. Confirm terminal labels, contact states, alarm text, trend names and the response expected after a signal failure. Where a cooling stage is controlled by temperature, verify both operation and reset so the equipment does not remain energized or cycle unexpectedly.

Record the final settings, wiring, remote scaling and functional test. These records allow maintenance teams to separate an instrument problem from a wiring, receiving-system or transformer operating issue, and they provide the information needed for a future BWY2-804 and BWY2-806 variants replacement.

Information to Send for a Quote

  • Complete BWY2 model suffix
  • Top-oil temperature scale
  • Two to four contact functions
  • Pt100 or transmitter output
  • Bulb, thread and pocket
  • Capillary and mounting position

Also include the quantity, destination country, required date and any existing nameplate, wiring or installation drawings. Ask for the current datasheet, outline drawing and terminal diagram for the selected configuration.

State whether the inquiry is for new transformer production, a planned retrofit or an urgent replacement. This helps the sales and engineering team focus on the correct model, compatibility checks, documentation and packing requirements. Include the transformer rating and installation environment so the proposed instrument can be reviewed in the correct operating context.

View the BWY2-804 and BWY2-806 variants product page before sending your inquiry.

Sales and engineering support

Request a Datasheet and Quote

Tell us the transformer type, required temperature range, contact functions, output signal, capillary length, quantity and destination. We will help you identify a suitable model and send the available technical documents.